Modelling IFC SG for SCDF Submission

Modelling IFC-SG for SCDF Submission

The following fire safety equipment / provision need not be shown in the model.

  • Equipment, furniture, fixture (e.g. lighting, fans)
  • Wiring connecting various system in building
  • Netting with more than 50% opening
  • Intumescent paint
  • Flame retardant chemical
  • Detailed composition of composite panel

The following fire safety equipment / provision need not be modelled in full.

They can be represented by suitable objects.

If the equipment / provision is applicable only to Independent Submission, they can be represented in 2D.

  • Signage (exit staircase numbering, evacuation lift, re-entry floor, etc)
  • Signage for “PWD Holding Point”
  • Mean of communication between PWD holding point and FCC/24 hourly manned station.
  • Override device
  • Fire stopping material (for filling gap)
  • Composite panel
  • Hose reel drum (excluding cabinet/enclosure)
  • Breathing apparatus cabinet/enclosure (for Total flooding fire extinguishing system)
  • Generator/emergency generator/standby generator
  • Transformer
  • Fire extinguisher
  • Housing cabinet/enclosure
  • Main fire alarm panel/cabinet
  • Sub fire alarm panel/cabinet
  • Manual call point
  • Standby hose cabinet/enclosure
  • Bell for manual alarm
  • Vision alarm – strobe light
  • Smoke/heat detector
  • Home Fire Alarm Device (HFAD)
  • Video Image Fire Detection System (VIFDS)
  • Sprinkler head
  • Sprinkler control valve
  • Fire pump & control panel
  • Fire water tank
  • Compressed cylinders & discharge nozzle for Water mist system
  • Compressed cylinders & discharge nozzle for fixed automatic fire extinguishing systems (e.g kitchen suppression system, GM200, etc)
  • Fire lift switch
  • Evacuation switch
  • Intercom system in fire lift
  • CCTV camera
  • Lift control panel
  • Lift car
  • Standby fans/multiple fans
  • Fire damper
  • Smoke damper
  • Air-handling unit
  • Air conditioner compressor + unit
  • Exit/directional exit sign (high level and low level)
  • Exit/directional exit sign (high level and low level)
    • Need to provide arrow if for directional exit sign
  • Emergency lighting
  • Photoluminescent marking
  • Equipment/services in Fire Command Centre mentioned in Cl. 8.2.4b.
  • Speakers for public address system/emergency voice communication system
  • Handset/cabinet/enclosure (for emergency voice communication system)

 

Link: IFC-SG Resource Kit

See also: Preparing models for submission